If the burners shut off within seconds of lighting, suspect a dirty flame sensor. If they run several minutes and then stop while the blower keeps going, the furnace is overheating, usually from a clogged filter or blocked airflow. Pressure switch or condensate problems cause shutdowns before or right after ignition.
Use the timing to narrow it down
| When it shuts off | Most likely cause | Learn more |
|---|---|---|
| 3–10 seconds after the burners light | Dirty flame sensor | Flame sensor |
| Several minutes in; blower keeps running | Overheating: high-limit switch trip | Limit switch |
| Before ignition, after the inducer runs | Pressure switch, condensate trap or venting | Condensate drain |
| Random times, thermostat display flickers | Thermostat power or wiring | Thermostat checks |
| Short, frequent cycles that do reach temperature | Short cycling: oversizing or thermostat location | Short cycling |
Overheating: the most common cause
A furnace needs steady airflow to carry heat away from the heat exchanger. When airflow drops, the temperature climbs until the high-limit switch shuts off the burners. The blower keeps running to cool things down, then the cycle repeats. Causes, in order of how often we see them in Schertz:
- Clogged filter, especially in winter when cedar pollen peaks
- Closed or blocked vents and returns (furniture, rugs, closed doors to rooms with returns)
- Dirty blower wheel or weak blower motor
- Crushed, kinked or undersized attic ducts
Overheating isn't just annoying. Repeated limit trips stress the heat exchanger, one of the main causes of cracks.
What you can do now
- Replace the filter, even if it's not due.
- Open every supply vent and clear returns.
- Set the thermostat fan to AUTO.
- Check the drain pan under attic units for standing water.
A tripped rollout switch is different. If a technician finds the rollout switch tripped, it means flames escaped the burner area, possibly from a blocked flue or a damaged heat exchanger. It needs inspection, not just a reset.
When to call
If a new filter and open vents don't fix it within a day, or the furnace shuts off within seconds of lighting, call for service. These problems are usually affordable fixes, like flame sensor cleaning, switch testing or drain clearing, when caught early.